Cable Test

Home Electronics E-mail Notes Meetings Subsystems Search

Cable Test in Chicane Mock up

Several type of cables have already been installed and tested in the chicane mock up in building 157 at CERN. Those tests will allow us to determine more precisely the packing factor to be considered for the installation in the cavern. It will also give us a more realistic view on the total cross section that is really needed, especially for the passage through the shielding wall. Once the cables are tested, the values in the existing cable lists will be modified.

These tests also gave us the possibility to measure and determine the minimum bending radius for the main electrical distribution cables (for TS-EL).

Results :

Type Description SCEM Potential user Diameter [mm] Total cross section (insulation included) [mm2] Minimum bending radius [mm] * Weight /  cable Tested Tested number of cable in a 3dm2 cable tray (from tests in mock-up) Minimum packing factor to be applied **
Optical fiber ribbon 12 fiber ribbon No SCEM All LHCb detectors 2.3 * 5.1 12 - ? no  to be tested 1.5 (estimated)
Single power cable installation cable 95mm2 04.08.61.406.8 ??? 17.2 233 - ?  no  to be tested 1.7 (estimated)
High voltage power cable Coax cable for 20kV 04.31.51.775.2 Rich 7.6 46 - ? yes 392 1.7
High voltage power cable Multi-wire HV cable (3kV) 04.31.52.100.5 OT, ST 14 154 - ? yes 133 1.5
Multi-wire power cable multi wires NF48P 04.21.52.175.3 VELO 23.5 434 ~310 ? yes 44 1.57
Signal cable CAT 6 04.21.70.104.6 VELO, (SPECS) 6 29 - 28 kg/km yes 774                           (188 occuped 7280mm2) 1.34
Main electrical distribution NUVOA FULGORCAVI 240mm2 3,3kV (super souple) - TS/ EL ~32 804 ~250 ? yes 24 (4 tested :space for 8x3 in 3dm2) 1.6
Main electrical distribution AEG KABEL RHEYHALON 240mm2 1kV - TS/ EL ~28 616 ~400 ? yes 21 ( 5 tested :space for 7x3 in 3dm2)  2.4
Main electrical distribution 0,6/1kV FR N1x1G1 R 400mm2 - TS/ EL ~32 804 ~580 ? yes 12 ( 2 tested: space for 4x3 in 3dm2) 3.2
* : If not specified the bending radius should be considered as 10 times the cable diameter
** : The packing factors to be applied for the cable trays definition will be with some safety margin 

CAT6  Signal cables ( 4x2 diam 5,8mm ) SCEM : 04.21.70.104.6 

376 cables tested in a 1,5 dm2 "Cablofil" cable tray

Results

 

Multi wires NF48P Power cables ( 24 x 2 x 0,75mm2 ) SCEM : 04.21.52.175.3 

44 cables tested in a 3 dm2 "Cablofil" cable tray

Results

 

Multi HV Power cables ( 56 wires ) SCEM : 04.31.52.100.5 

133 cables tested in a 3 dm2 "Cablofil" cable tray

Results

 

20 kV HV Power cable ( coax cable ) SCEM : 04.31.51.775.2 

392 cables tested in a 3 dm2 "Cablofil" cable tray

Results

 

Power Supply Cable 1   NUVOA FULGORCAVI 240mm2 3,3kV (super souple)

4 cables tested in 1,5 dm2 Cable Try

Results

 

Power Supply Cable 2   AEG KABEL RHEYHALON 240mm2 1kV

5 cables tested in 1,5 dm2 Cable Try

Results

 

Power Supply Cable 3   0,6/1kV FR N1x1G1 R 400mm2

2 cables tested in 1,5 dm2 Cable Try

Results