Job Information

Job ID: Date: 07.09.2007 10:42:34
Reason:
Contractor: Operator A:
Customer: Operator B:
Custom job 1: Custom job 2:

Cable Information

Cable ID: 10008_6    
Location A: Location B:
Cable Mfr.: Cable Type:
Custom cable 1: Custom cable 2:

System Information

  Unit A Unit B
Unit Name: FOT-930 FOT-932
Serial Number: 417390 417389

FasTesT

Fiber ID
Wavelength
 
(nm)
Loss
A->B
(dB)
Ref.
A->B
(dB)
Loss
B->A
(dB)
Ref.
B->A
(dB)
Average
 
(dB)
ORL
A
(dB)
ORL
B
(dB)
Length
 

(km)
FIBER001 1300 0.05 3.09 0.09 3.27 0.07    
-0.049
(07.09.2007 10:42:43)
FIBER002 1300 0.01 3.09 0.03 3.27 0.02    
-0.050
(07.09.2007 10:43:05)
FIBER003 1300 1.09 3.09 1.10 3.27 1.10    
-0.049
(07.09.2007 10:43:25)
FIBER004 1300 0.85 3.09 0.84 3.27 0.85    
-0.049
(07.09.2007 10:43:44)
FIBER005 1300 0.41 3.09 0.38 3.27 0.39    
-0.050
(07.09.2007 10:44:03)
FIBER006 1300 0.38 3.09 0.42 3.27 0.40    
-0.049
(07.09.2007 10:44:20)
FIBER007 1300 -0.11 3.09 -0.10 3.27 -0.11    
-0.049
(07.09.2007 10:44:40)
FIBER008 1300 -0.26 3.09 -0.27 3.27 -0.27    
-0.050
(07.09.2007 10:45:01)
FIBER009 1300 -0.28 3.09 -0.28 3.27 -0.28    
-0.050
(07.09.2007 10:45:23)
FIBER010 1300 0.18 3.09 0.19 3.27 0.18    
-0.049
(07.09.2007 10:45:40)
FIBER011 1300 0.50 3.09 0.49 3.27 0.50    
-0.050
(07.09.2007 10:45:56)
FIBER012 1300 0.50 3.09 0.50 3.27 0.50    
-0.050
(07.09.2007 10:46:20)